Title: Comparative analysis between ROCOF and vector surge relays for distributed generation applications
Author: Freitas, W
Xu, WS
Affonso, CM
Huang, ZY
Abstract: This paper presents a comprehensive comparative analysis between rate-of-change-of-frequency (ROCOF) and vector-surge (VS) relays for distributed generation islanding detection. The analysis is based, on the concepts of detection-time versus active power-imbalance curves and critical active power imbalance. Such curves are obtained through dynamic simulations. The performance of these devices considering different scenarios is determined and compared. Factors such as voltage-dependent loads, generator inertia constant, and multidistributed generator systems are analyzed. False operation of these relays due to faults in adjacent feeders is also addressed. Results show that ROCOF relays are more reliable to detect islanding than vector surge relays when the active power imbalance in the islanded system is small. However, ROCOF relays are more susceptible to false operation than VS relays.
Subject: distributed generation
islanding detection
rate of change of frequency (ROCOF) relays
vector-surge (VS) relays
Country: EUA
Editor: Ieee-inst Electrical Electronics Engineers Inc
Rights: fechado
Identifier DOI: 10.1109/TPWRD.2004.834869
Date Issue: 2005
Appears in Collections:Unicamp - Artigos e Outros Documentos

Files in This Item:
File Description SizeFormat 
WOS000228096100013.pdf473.07 kBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.