Please use this identifier to cite or link to this item: http://repositorio.unicamp.br/jspui/handle/REPOSIP/347416
Type: Artigo
Title: Relevant parameters in a statistical analysis: application to transmission-line energization
Author: Mestas, P.
Tavares, M.C.
Abstract: This paper summarizes the important factors that affect statistical switching transients studies during transmission-line energization. These factors include the number of repetitions to ensure the statistical characteristic of the study, the variation range of the mean closing time of the circuit-breaker contacts, the model used for the representation of the transmission line, and the influence of transposition. In addition, a statistical analysis of mitigation methods to reduce overvoltages during transmission-line energization maneuver is presented, specifically the use of surge arresters, of controlled switching, and of a preinsertion resistor. The shunt compensation degree is considered as an independent parameter. Digital simulations were performed with PSCAD
Subject: Energia elétrica - Transmissão
Country: Estados Unidos
Editor: Institute of Electrical and Electronics Engineers
Rights: Fechado
Identifier DOI: 10.1109/TPWRD.2014.2317875
Address: https://ieeexplore.ieee.org/document/6847243
Date Issue: 2014