Please use this identifier to cite or link to this item: http://repositorio.unicamp.br/jspui/handle/REPOSIP/347357
Type: Artigo
Title: Comparison between traditional single-phase auto reclosing and adaptive technique based on harmonic content measurement
Author: Dias, Ozenir
Tavares, Maria Cristina
Abstract: This study presents the results of single-phase auto reclosing technique tests, comparing the performance of traditional procedure and fast adaptive procedure. The last is based on the measurement of voltage harmonic content on the transmission line faulty phase terminals. The transmission system used was modelled on the real-time digital simulator with a distance relay and a quality meter to more realistically implement the reclosing techniques. The studied system was based on an actual Brazilian 500 kV transmission system. This study highlights the advantages of using the adaptive technique opposite to the use of traditional manoeuvre
Subject: Energia elétrica - Transmissão
Country: Reino Unido
Editor: Institution of Engineering and Technology
Rights: Fechado
Identifier DOI: 10.1049/iet-gtd.2016.0849
Address: https://ieeexplore.ieee.org/document/7876914
Date Issue: 2017
Appears in Collections:FEEC - Artigos e Outros Documentos

Files in This Item:
File Description SizeFormat 
000398589300010.pdf1.7 MBAdobe PDFView/Open