Please use this identifier to cite or link to this item:
http://repositorio.unicamp.br/jspui/handle/REPOSIP/347342
Type: | Artigo |
Title: | Energization simulations of a half-wavelength transmission line when subject to three-phase faults: application to a field test situation |
Author: | Silva, Eduardo A. Moreira, Fernando A. Tavares, Maria C. |
Abstract: | The purpose of this paper is to supply technical data for the proposed field energization of 500 kV transmission lines present in the Brazilian interconnected system, forming a line, henceforth called AC-Link, slightly over a half-wavelength in 60 Hz. The purpose of the test is to investigate overvoltages and currents that result from the energization of the AC-Link. This paper shows the results of simulations performed in ATP (Alternative Transients Program) when considering the occurrence of three-phase faults along the AC-Link during energization. The results obtained show that, in certain situations, the overvoltages and energies in the arresters may reach very high values and some specific mitigation procedure should be implemented |
Subject: | Pára-raios |
Country: | Países Baixos |
Editor: | Elsevier |
Rights: | Fechado |
Identifier DOI: | 10.1016/j.epsr.2016.03.029 |
Address: | https://www.sciencedirect.com/science/article/pii/S0378779616300761 |
Date Issue: | 2016 |
Appears in Collections: | FEEC - Artigos e Outros Documentos |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
000379374300009.pdf | 2 MB | Adobe PDF | View/Open |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.