Please use this identifier to cite or link to this item: http://repositorio.unicamp.br/jspui/handle/REPOSIP/347184
Type: Artigo
Title: Analysis of half-wavelength transmission line under critical balanced faults: voltage response and overvoltage mitigation procedure
Author: Santiago, Javier
Tavares, Maria Cristina
Abstract: This paper presents a detailed study of half-wavelength (HWL) transmission line system under critical fault conditions. This non-conventional ultra high voltage alternating current (UHVAC) transmission line has excellent properties in steady-state operation condition and economic advantage when compared to conventional UHVAC system and even high voltage direct current (HVDC) transmission systems for similar power capacity. This technology has been studied for many decades and its response under condition fault is an important topic. First, the point of fault and the type of fault conditions are evaluated to confirm that balanced faults in specific regions are critical. Then the main characteristics of voltage response of HWL transmission system under balanced fault are presented and critical regions that produce severe overvoltage are identified and main transient characteristics are described. Finally, a preliminary mitigation procedure is shown and its performance is evaluated
Subject: Arco elétrico
Country: Países Baixos
Editor: Elsevier
Rights: Fechado
Identifier DOI: 10.1016/j.epsr.2018.10.002
Address: https://www.sciencedirect.com/science/article/pii/S0378779618303195
Date Issue: 2019
Appears in Collections:FEEC - Artigos e Outros Documentos

Files in This Item:
File Description SizeFormat 
000452936200011.pdf5.78 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.