Please use this identifier to cite or link to this item: http://repositorio.unicamp.br/jspui/handle/REPOSIP/336787
Type: DISSERTAÇÃO DIGITAL
Degree Level: Mestrado
Title: Uso de medições para avaliação e mitigação de perdas em transformadores de distribuição : estudo de caso no laboratório vivo da Unicamp
Title Alternative: Using measurements for assessment and mitigation of losses in distribution transformers : case study in the living lab of Unicamp
Author: Puma Flores, Fransk Abdel, 1995-
Advisor: Almeida, Madson Cortes de, 1973-
Abstract: Resumo: As perdas em transformadores representam aproximadamente um terço das perdas totais que ocorrem em um sistema elétrico de distribuição. Entre estas, destacam-se as perdas em transformadores de distribuição, que podem afetar significativamente a eficiência energética e a sustentabilidade financeira. Devido à pouca disponibilidade de tecnologias de monitoramento, a gestão técnica e econômica nas fases de planejamento e operação dos transformadores de distribuição é precária e, portanto, se baseia em metodologias conservadoras, resultando em um agravamento da eficiência energética. Soluções integradas para o monitoramento e controle de sistemas elétricos fornecem condições adequadas para a estimativa e gerenciamento de perdas elétricas em sistemas de distribuição. Uma alternativa adotada para os transformadores de distribuição é o monitoramento por meio de medidores de energia conectados no lado de baixa tensão onde os dados medidos fornecem informações reais sobre o estado de operação da rede. Este trabalho enfoca a estimativa de perdas elétricas e o gerenciamento de transformadores de distribuição instalados no alimentador BGE-06 do campus de Barão Geraldo da Universidade Estadual de Campinas (UNICAMP). Atualmente, a rede elétrica da UNICAMP passa por um processo de modernização que culminará no monitoramento completo em tempo real de toda a rede, criando um laboratório vivo para estudos de redes elétricas. Neste contexto, foi realizada a coleta e o tratamento dos dados medidos nos terminais de transformadores para obter as curvas típicas de tensões, correntes e potências que são utilizadas para estimar com maior precisão as perdas elétricas dos transformadores. Em seguida, através de uma abordagem técnica e econômica são apresentadas alternativas para o gerenciamento dos transformadores. Os estudos apresentados apontam a viabilidade das estratégias de gestão, as quais resultam em redução das perdas elétricas. Os resultados mostraram das alternativas um Payback para um cenário conservados a partir de 5 anos e para um cenário otimista a partir de 4 anos. Nas análises são considerados custos da energia, da aquisição e instalação de transformadores e implementação do sistema de monitoramento

Abstract: Transformer losses represent approximately one-third of the total losses that occur in an electrical system. These include losses in distribution transformers, which can significantly affect energy efficiency and financial sustainability. Due to the low availability of monitoring technologies, the technical and economic management in the planning and operation phases of the distribution transformers is precarious and, therefore, based on conservative methodologies, resulting in a worsening of energy efficiency. Integrated solutions for the monitoring and control of electrical systems provide suitable conditions for the estimation and management of electrical losses in distribution systems. An alternative adopted for distribution transformers is monitoring through smart meters connected on the low voltage side where the measured data provides real information about the operating state. This work focuses on the electric loss estimation and distribution transformer management installed on the feeder BGE-06 of the Barão Geraldo campus at University of Campinas (UNICAMP). Today, UNICAMP electrical system goes through a modernization process that will culminate in the complete monitoring of the entire system in real-time, raising a live laboratory for studies of the electrical system. In this context, the data measured at the transformer terminals were collected and processed to obtain the typical voltage, current and power curves that are used to more accurately estimate the electrical losses of the transformers. Then, through a technical and economic approach, alternatives for transformer management are presented in this work. The studies presented indicate the viability of management strategies, which result in a reduction of electrical losses. The results showed from the alternatives a Payback for a scenario conserved from 5 years and for an optimistic scenario from 4 years. The analysis considers energy costs, the acquisition and installation of transformers and the implementation of the monitoring system
Subject: Perdas elétricas
Transformadores elétricos
Medidas elétricas
Eficiência energética
Geração distribuída de energia elétrica
Language: Português
Editor: [s.n.]
Citation: PUMA FLORES, Fransk Abdel. Uso de medições para avaliação e mitigação de perdas em transformadores de distribuição: estudo de caso no laboratório vivo da Unicamp. 2019. 1 recurso online (112 p.). Dissertação (mestrado) - Universidade Estadual de Campinas, Faculdade de Engenharia Elétrica e de Computação, Campinas, SP.
Date Issue: 2019
Appears in Collections:FEEC - Tese e Dissertação

Files in This Item:
File SizeFormat 
PumaFlores_FranskAbdel_M.pdf5.86 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.