Title: Energization Simulations Of A Half-wavelength Transmission Line When Subject To Three-phase Faults-application To A Field Test Situation
Author: Silva
EA; Moreira
FA; Tavares
MC
Abstract: The purpose of this paper is to supply technical data for the proposed field energization of 500 kV transmission lines present in the Brazilian interconnected system, forming a line, henceforth called AC-Link, slightly over a half-wavelength in 60 Hz. The purpose of the test is to investigate overvoltages and currents that result from the energization of the AC-Link. This paper shows the results of simulations performed in ATP (Alternative Transients Program) when considering the occurrence of three-phase faults along the AC-Link during energization. The results obtained show that, in certain situations, the overvoltages and energies in the arresters may reach very high values and some specific mitigation procedure should be implemented. (C) 2016 Elsevier B.V. All rights reserved.
Subject: Half-wavelength
Three-phase Fault
Overvoltage
Surge Arrester
Line Energization
Atp
Editor: ELSEVIER SCIENCE SA
Rights: fechado
Identifier DOI: 10.1016/j.epsr.2016.03.029
Address: http://www-sciencedirect-com.ez88.periodicos.capes.gov.br/science/article/pii/S0378779616300761
Date Issue: 2016
Appears in Collections:Unicamp - Artigos e Outros Documentos