Please use this identifier to cite or link to this item: http://repositorio.unicamp.br/jspui/handle/REPOSIP/262010
Type: DISSERTAÇÃO DIGITAL
Degree Level: Mestrado
Title: Eliminação de sobrecargas em sistemas de transmissão através do chaveamento de ramos
Title Alternative: Elimination of transmission systems overloads through branch switching
Author: Pinheiro, Daniel da Conceição, 1987-
Advisor: Castro Junior, Carlos Alberto de, 1960-
Junior, Carlos Alberto de Castro
Abstract: Resumo: Este trabalho tem como objetivo contribuir para o desenvolvimento de métodos para o alívio de sobrecargas em sistemas de transmissão. Dentre as várias alternativas possíveis para a realização desta tarefa está o chaveamento de ramos (linhas de transmissão e transformadores). Embora esta possibilidade já seja conhecida, recentemente foi proposto um método bastante interessante para a identificação dos ramos a serem chaveados. Neste trabalho, a ideia é propor melhorias neste método, de forma a torná-lo eficiente para utilização em ambientes de monitoramento e controle em tempo real. O método proposto é baseado na combinação da análise de sensibilidade com técnicas de busca local adaptativa, que encontram ações de controle de boa qualidade para o alívio das sobrecargas, evitando efeitos indesejáveis, tais como o surgimento de novas sobrecargas e violações de tensão. O algoritmo foi implementado na plataforma MATLAB®, utilizando o fluxo de carga da ferramenta computacional MATPOWER. As simulações presentes neste trabalho foram realizadas em redes do sistema IEEE e do sistema interligado nacional (SIN)

Abstract: This work aims to contribute to the development of methods for alleviating overloads in the transmission system. Among the several possible alternatives to achieve this goal, branch (transmission lines and transformers) switching will be the focus in this work. Even though this possibility is well-known, a very interesting branch switching method was proposed recently in the literature to identify the candidate branches to be switched. In this work the idea is to propose improvements to this method in such a way it becomes efficient enough to be used in real time monitoring and control environments. The proposed method is based on the combination of the sensitivity analysis with adaptive local search techniques, which find good quality branch switching actions for relieving overloads, avoiding side effects such as new overloads and voltage violations. The algorithm was implemented with MATLAB® using the load flow from MATPOWER. The simulations presented in this work involve IEEE networks and the full, interconnected Brazilian power system with 4,526 buses
Subject: Sistemas de energia elétrica - Análise
Energia elétrica - Transmissão
Sistemas de energia elétrica - Segurança
Topologia de redes elétricas
Redes elétricas
Editor: [s.n.]
Date Issue: 2016
Appears in Collections:FEEC - Tese e Dissertação

Files in This Item:
File SizeFormat 
Pinheiro_DanieldaConceicao_M.pdf3.62 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.