Title: Religamento monopolar adaptativo rapido baseado na assinatura harmonica da tensão de arco secundario
Title Alternative: Fast adaptive single-phase autoreclosing based on secondary arc voltage harmonic signature
Author: Montanari, Allan Alves
Advisor: Tavares, Maria Cristina Dias, 1962-
Abstract: Resumo: Este trabalho apresenta um esquema de religamento monopolar adaptativo rápido para otimizar o tempo compreendido entre a abertura e o religamento da fase sob falta. A proteção adaptativa recompõe rapidamente o sistema de transmissão de energia elétrica, minimizando a probabilidade de propagação de perturbações severas no sistema. O método é fundamentado na análise de dados de ensaios de arco secundário gerados e monitorados numa estrutura de testes construída em campo, composta por um trecho real de linha de transmissão (três torres e dois vãos). Analisou-se o conteúdo harmônico da tensão e da corrente de arco secundário através da aplicação da Transformada de Fourier Janelada. Tais análises viabilizaram a realização de um tratamento estatístico para a caracterização da assinatura harmônica de arco secundário. Simulações de faltas monofásicas foram realizadas utilizando dados provenientes dos Ensaios de arco secundário. Desenvolveu-se um algoritmo baseado nas características Harmônicas da tensão da fase sob falta, calculadas através do deslocamento de uma janela de tempo sobre os sinais analisados (Transformada de Fourier Janelada). O algoritmo determina a existência do arco secundário e fornece informações a respeito do instante no qual o religamento pode ser realizado com sucesso. O método apresenta também um mecanismo para a detecção da característica permanente ou transitória da falta.

Abstract: This work presents a fast adaptive single-phase autorec1osingseheme to optimize the period between the tripping operation and the rec10sure of the faulted phase breakers. The adaptive proteetion quiekly reeomposes the eleetric power transmission, minimizing the probability of severe damages propagation in the system. The method is based on the analysis of secondary are field tests data that were generated and monitored in an infra-structure which consists of a real transmission line section (three towers and two spans). The harmonic content of the secondary are voltage and eurrent was analyzed by the application of Short Time Discrete Fourier Transform. Such analysis made it possible to implement a statistical approach in order to obtain the secondary are harmonic signature. Single-phase faults computer simulations were performed using the data obtained from the secondary are tests. It was developed an algorithm based on the voltage harmonic content of the faulted phase, which was ea1culated by shifting a window on the analyzed signals (Short Time Discrete Fourier Transform). The algorithm determines the secondary are existence and provides information in order to suceessfully rec10se the circuit breaker. The method also presents a control mechanism responsible for identifying whether the fault is a permanent one or a transient fault.
Subject: Linhas elétricas aéreas
Transitórios (Eletricidade)
Language: Português
Editor: [s.n.]
Date Issue: 2009