Please use this identifier to cite or link to this item: http://repositorio.unicamp.br/jspui/handle/REPOSIP/259527
Type: DISSERTAÇÃO
Degree Level: Mestrado
Title: Análise de observabilidade baseada em variâncias de medidas estimadas = Observability analysis based estimated measures variances
Title Alternative: Observability analysis based estimated measures variances
Author: Oliveira, Wilson Aparecido de
Advisor: Almeida, Madson Cortes de, 1973-
Abstract: Resumo: Este trabalho apresenta uma metodologia completa para analise de observabilidade de sistemas de energia eletrica. A observabilidade da rede e determinada a partir do traco da matriz de covariancia das medidas estimadas, as variancias dos fluxos estimados permitem a identificacao das ilhas observaveis e a restauracao da observabilidade e realizada a partir das variancias das medidas estimadas. As variancias necessarias sao obtidas da matriz de ganho linearizada regularizada. Alem das medidas disponiveis, na formacao da matriz de ganho regularizada admite-se a existencia de pseudomedidas de angulo em todas as barras da rede. O estimador de estado linearizado regularizado e a metodologia de identificacao de ramos observaveis a partir das variancias dos fluxos estimados foram apresentados em [Almeida, Garcia e Asada, 2011]. As novas contribuicoes deste trabalho sao o mecanismo de verificacao da observabilidade, baseado no traco da matriz de covariancia das medidas estimadas, o mecanismo de restauracao da observabilidade, desenvolvido a partir da analise das variancias das medidas, e a inclusao de medicao fasorial sincronizada na formulacao matematica utilizada

Abstract: The purpose of this work is to present a complete methodology for observability analysis of electric power systems. The observability of the network is determined from the trace of the covariance matrix of the measurement estimate, the variance of the estimated power flow allow the identification of observable islands and the restoration of observability is performed from the variance of the measurement estimate. The variances required are obtained from the regularized linearized gain matrix. Besides the measurements available, in the formation of regularized gain matrix allows the existence of voltage angle pseudomeasurements on all buses of the network. The regularized least squares power system state estimation and the methodology of analysis of the variance of the estimated power flow is based in [Almeida, Garcia e Asada, 2011]. The new contributions of this work are the observability checking mechanism, based on the trace of the covariance matrix of the measurement estimate, the mechanism of restoration of observability, developed from the analysis of variance of the measurement and the inclusion of synchronized phasor measurement in the mathematical formulation utilized
Subject: Sistemas de energia elétrica - Estimação de estado
Estimação de estado generalizado
Sistemas de energia elétrica
Análise de covariância
Análise de variância
Observadores (Teoria do controle)
Language: Português
Editor: [s.n.]
Date Issue: 2012
Appears in Collections:FEEC - Tese e Dissertação