Please use this identifier to cite or link to this item: http://repositorio.unicamp.br/jspui/handle/REPOSIP/106371
Type: Artigo de periódico
Title: Man-machine Interface For The Control Of Cooling Processes With Forced-air Aimed At Energy Savings [interface Homem-máquina Para Controle De Processos De Resfriamento Com Ar Forçado Visando à Economia De Energia]
Author: Teruel B.
Silveira P.
Marques F.
Cappelli N.
Abstract: The development of micro processed equipment is presented, with current exit for control of the speed of rotation of the fan motor of the system of forced air, using investing of the frequency. Through programming (software IHM.EXE), the user can define the mass to be cooled, in kilograms of the product. The equipment calculates through a programmable polynomial previously defined, the frequency of operation of the investor which corresponds to air specific flux, within the limits of the project. The equipment was installed in a forced-air cooling system, being considered by the calculation in useful mechanical power, the energy savings is estimated at around 82% with a rotation equivalent to 56% of the fan nominal, thus providing significant savings in system operating costs.
Editor: 
Rights: aberto
Identifier DOI: 10.1590/S0103-84782008000300017
Address: http://www.scopus.com/inward/record.url?eid=2-s2.0-42249115364&partnerID=40&md5=5e2504575c249be8a83fc43e4bed635d
Date Issue: 2008
Appears in Collections:Unicamp - Artigos e Outros Documentos

Files in This Item:
File SizeFormat 
2-s2.0-42249115364.pdf99.97 kBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.